Any questions? +36703252122 or info@pvsolarstore.com

DC Surge Protector SUNTREE 3P SUP2H-PV T2 1000V DC 20-40KA

Product type
DC SPD
Item
SUP2H-PV T2
Wave Type
Type II (T2)
Protection level B,C,D Grade
D,C,B
Discharge Current
500VDC/800V/1000VDC
Nominal discharge current
7KA
Max-Discharge Current
20KA/40KA/60KA
Protection Level(In)Up
≤2.8KV/4.5KV
Number of Poles
3P
Operating temperature
-40℃~+85℃
Test standards
GB/T118802.1,IEC61643-31
Available for pre-order
Details

Application

The Cooper Suntree three-module photovoltaic Surge Protective Device (SPD) (with three-step DC switching device) features visual indication and optional remote contact signaling (floating changeover contact) for use in PV systems. These complete surge protective devices are suitable for all PV systems in accordance with IEC 60364-7-712. Includes a five year limited warranty.

These pre-wired solutions consist of a base and locking modules that feature a combined disconnection and short-circuiting (shunting) device with safe electrical isolation to prevent fire damage due to DC arcs. An integrated DC fuse allows safe module replacement without arc formation. In case of insulation faults in the generator circuit, a reliable and tested fault-resistant `l circuit prevents damage to the surge protective devices.

The green and red visual indicator flags show the module protective status (green = good, red = replace). Apart from this visual indication,the remote signaling option features a three terminal floating changeover contact that can be used as a make or break contact depending on the particular monitoring system design employed.

Dimension

Short-Circuit Interrupting (SCI) Technology

Specifications

SUP2H-PV series surge protector SUP2H1-PV SUP2H1-PV SUP2-PV
UCPV(VDC) 1000V 1200V 1500V
Max system discharge current (8/20μs)Imax 40KA 40KA 40KA
Voltage Protection level(up) ≤4.0KV ≤4.5KV ≤4.5KV
Voltage Protection level at 5kA(up) ≤3.6KV ≤4.0KV ≤5.0KV
Integrated Fuse breaking capacity/interrupting rating 40KA/1000vdc 40KA/1200vdc 40KA/1500vdc
technology Short-Circuit interruption (SCI)overcurrent protection
Operating temperature range(TU) -40℃ to +80℃
Nominal discharge current (8/20 μs){(DC+/DC-)>PE}(In) 20KA
Response time (A) <25ns
Operating State/Fault indication Green (good)/RED(repiace)
Conductor rating and cross-sectional Area Minimum 60/75℃ 1.5mm2/14AWG solid/flexible
Maximum 60/75℃ 35mm2/2AWG stranded/25mm2/4AWG flexible
Mounting 35mm DIN rall per EN 60715
Enclosure material UL 90VO thermopiastic
Degree of Protection IP20
Capacity 3 Modules,DIN 43880
Standards information IEC 61643-31 Type2,IEC 61643-1 ClassⅡ
product Warranty Five Years

Remote Contact signaling​

Remote Contact signaling Type Changeover contact
AC switching capacity(volts/Amps) 250V/0.1A
DC switching capacity(volts/Amps) 250V/0.1A;125V/0.2A;75V/0.5A
Conductor ratings and cross-sectional area for remote
Contact signal terminals
60/75℃Max,1.5mm2/14AWG solid/flexible
Ordering Order from Catalog numbers Above

Typical Application Schematics

Does not apply to 1200Vdc
1.Use a suitable electrical insulator to keep a 10mm min.safety distance from the PV-SPD and other grounfed parts in the housing.
2.No metal covers are in the area of the module release as shown.

Conductor and busbars for use in photovoltaic systems
IEC 60364-7-712(DIN VDE 0100 part 712)

Info
Manufacturer
Suntree
Number of Poles
3
Nominal Voltage
1000 V
Protection Class
T2
Article No.
402403100051
Weight
350 g/pcs
Additional products
Similar products